Re: If all 3 are single-point-grounded, why does A/C need a surge suppressor but phone & cable do not?

From: w_tom (w_tom1_at_hotmail.com)
Date: 07/09/04


Date: Fri, 09 Jul 2004 18:51:02 -0400


  Protection is required for every incoming wire to a building
including satellite dish and television antenna. But National
Electrical Code is not concerned with appliance safety. Their
mandate is for human safety. Therefore 'whole house'
protector on phone wires and grounded cable wire is required
by code. 'Whole house' protector for AC electric is not
required. We still build new homes as if the transistor did
not exist. No code exists to protect household appliances.
Therefore homeowner must complete the protection 'system'.

  Homeowner must exceed code requirements; install additional
appliance protection on AC electric. Intermatic products
(including the one sold in Home Depot as Intermatic IG1240RC)
can put 'whole house' protection on AC electric. Others are
sold by Leviton, Cutler Hammer, Ditek, Polyphaser, Furse,
Erico and a very long list of other manufacturers. Square D
also sells an integrated 'whole house' protector that does
everything in one rack:
  http://makeashorterlink.com/?Z1B7539A1
which should not be confused with an older Square D product
that
is undersized (ineffective).

  Earthing is required on every incoming wire. Some cable
companies are now (finally) earthing their cable before
entering the building (a ground connection to outside water
faucet is not acceptable protection). No surge protectors
required to earth the incoming CATV wire. Telco routinely
installs a 'whole house' protector (for free) in the NID of
each customer interface. Again, these are required by code
and therefore (should) exist. But the most common source of
destructive surges is wires highest on utility pole; wires
most often struck - AC electric. For appliance protection, an
AC electric 'whole house' protector is important.

Flea Ridden wrote:
> Why don't all manufacturers sell models like the Intermatic
> PanelGuard IG1300-2T-1C which protects phone and cable
> inputs too?
>
> If protection like this is not needed for phone and cable
> lines, why is it needed for A/C lines?



Relevant Pages

  • Re: belkin power conditioner for my Samsung LCD - is it worth it???
    ... protection already inside the appliance. ... But to make that connection direct (from lightning's ... perspective) means that wire must be short, ... inside appliances routinely makes those surges irrelevant. ...
    (alt.tv.tech.hdtv)
  • Re: Replacing 2-Prong Receptacles
    ... The ground wire is not needed and not used in the detection. ... GFCIs provide additional protection in locations where contact to metal ... provide fire protection but is primarily aimed at shock protection. ... For aGFCIinstalled on a 2 wire circuit ...
    (sci.engr.electrical.compliance)
  • Re: Lightning and computer?
    ... Does every incoming utility wire make a 'less than 10 ... That earth ground rod means nothing about earthing the ... the appliance internal protection saved those appliances. ... some appliances make a better connection to earth ...
    (microsoft.public.windowsxp.hardware)
  • Re: How to PostMortem?
    ... provide that all so essential common mode transient ... protection is about earthing - and where that earthing is ... AWG to connect to earth ground and water pipe. ... and wire to remove electricity from water pipe must be 6 AWG ...
    (comp.os.linux.setup)
  • Re: Replacing 2-Prong Receptacles
    ... The ground wire is not needed and not used in the detection. ... It is certainly a good idea to have a ground connection at the outlet. ... GFCIs provide additional protection in locations where contact to metal ... For aGFCIinstalled on a 2 wire circuit ...
    (sci.engr.electrical.compliance)