Re: modified PIC control loop

From: terry (the_domes_at_xtra.co.nz)
Date: 08/03/04


Date: Tue, 3 Aug 2004 14:42:53 +1200


"Terry Given" <the_domes@xtra.co.nz> wrote in message
news:j2gMc.4065$N77.263011@news.xtra.co.nz...
> "Tim Wescott" <tim@wescottnospamdesign.com> wrote in message
> news:10g2hsjrf0ovl3e@corp.supernews.com...
> > Rene Tschaggelar wrote:
> >
> > > The PID being the simples control loop in case an accurate model is
> > > somehow out of reach knows many enhancements to speed it up or
otherwise
> > > improve it. We face the problem that the control output is limited in
> > > reality. When the limit is reached, the integartor keeps integrating
> > > and the delay until it comes down again is felt as dead time. A
customer
> > > suggested to freeze the integrator when the outpout hits the rail.
While
> > > I investigated the subject ages ago, but apparently lost some
knowledge
> > > due to non-use.
> > > What is the drawback when I freeze the integrator ?
> > >
> > > Rene
> >
> > The problem is called "windup". I've never heard of freezing the
> > integrator when the output hits the rail -- that's an interesting one.
> >
> > The usual anti-windup scheme is to limit the integrator state. A good
> > first choice is to full-scale, but you may want to limit it to less than
> > full scale if you know that's all you'll need, i.e.:
> >
> > p_part = p_gain * in_error;
> > i_state += i_gain * in_error;
> > if (i_state > i_lim) i_state = i_lim;
> > else if (i_state < -i_lim) i_state = -i_lim;
> > return p_part + i_state;
> >
> > The anti-windup that I prefer is to hold the integrator state to that
> > necessary to just achieve full output (I can't thing of a clearer way of
> > putting that). So you do something like:
> >
> > p_part = p_gain * in_error;
> > i_state += i_gain * in_error;
> >
> > if (i_state + p_part > max_out) i_state = max_out - p_part;
> > else if (i_state + p_part < -max_out) i_state = -max_out - p_part;
> >
> > return p_part + i_state;
> >
> > The nice thing about this method is that the integrator is _never_ wound
> > up beyond the point where changes in the integrator state are not
> > immediately effective. In a well tuned loop it eliminates not only the
> > instability from integrator windup but also the "windup overshoot" that
> > you often see as well.
> >
> > Tim Wescott
>
> nice. And a hell of a lot simpler than most anti-windup schemes I have
> seen/played with which usually involve some sort of controller that varies
> Ki (or +/- Ilim) as a function of the commanded-versus-actual output
signal
> error. Then you have to tune the dynamics of the anti-windup loop.....
>
> If you use saturating arithmetic (eg a DSP), then you could could
calculate
> an offset to add to the integrator output to force saturation, then
subtract
> it again.
>
> Likewise it can be a good idea to limit the magnitude of in_error.
>
> Another good approach is to low-pass filter the reference signal - with
the
> same Fcross as the closed control loop. That way when you command a step
> change (which NO controller can EVER follow) you avoid exciting the loop
> unnecessarily. ramp-rate limiting of the reference is another way of
> achieving the same goal - prevent asking the controller for things it cant
> deliver.
>
> I like Internal Model Control.
>
>
> cheers
> Terry

Another problem that frequently arises is overshoot due to large-signal
behaviour - a large (step) change in reference invariably causes overshoot
due to the integrator. A very simple technique can greatly improve the
behaviour of a PID loop to such large signals, viz.:

conventional PID controller:

controller output U = (setpoint - plant output)*[Kp + Ki/s + Kd*s]

can be re-written as:
U(s) = A(s)*setpoint(s) - A(s)*plant_output(s)
A(s) = Kp + Ki/s + Kd*s

weighted PID controller:
U = (b*setpoint - plant output)*Kp + (setpoint - plant output)Ki/s +
(c*setpoint - plant output)*Kd*s

can be rewritten as
U(s) = B(s)*setpoint(s) - A(s)*plant_output(s)
A(s) = Kp + Ki/s + Kd*s
B(s) = b*Kp + Ki/s + c*Kd*s

simply setting b = c = 0 can make a dramatic improvement to the large-signal
response. other weights can of course be used. Astrom covers this in
detail...

cheers
Terry



Relevant Pages

  • Re: Bound control system
    ... Consider the PID controller and just the upper bound of error E. ... and the controller state is set to zero also. ... The problem is what to do with the integrator. ... Is it the torque or the velocity loop or just the position loop. ...
    (comp.dsp)
  • Re: Dumb question #102
    ... I want to loop through a table, and be able to pull out data from ... > Controller 2, Bob ... > MR3, Stephen, On Hold, Terry ... > Status and Controller for each row that I process? ...
    (microsoft.public.dotnet.framework.adonet)
  • Re: control law modification
    ... reject any steady-state disturbance from C, so the question is fair as ... You're being asked to make a _PD_ controller (one gain times proportional, ... settle to 0 (or zero steady-state error). ... When you integrate your error the output of the integrator is guaranteed ...